Getting Automist signed off by Building Control

Automist is accepted by Building Control all over the country, but it isn’t automatic. Here’s how sign-off works, and how to avoid the common problems.

Who decides

Building Control (your local authority or an approved inspector) decides whether your fire safety design meets the regulations. As installers we design the system to the brief, and we’ll give you everything you need for your submission, but the decision is theirs.

How water mist fits the regulations

Approved Document B is guidance. Where a design doesn’t follow it exactly, such as an open-plan layout, the regulations can be met by other acceptable means. For water mist, the usual route runs through BS 9991 (fire safety in residential buildings), which points to BS 5306-0, which in turn points to the water mist standard.

A note on the standards

For years the water mist standard was BS 8458:2015, and Automist holds a BSI Verification Certificate (VC 780009) against it. BS 8458 has now been withdrawn, because the new European standard BS EN 14972-17:2025 was published. That’s a procedural change, not a problem with the product: systems installed to BS 8458 remain valid, and it can still be used as a design basis where Building Control accepts it. Automist has been fire-tested to BS EN 14972-17:2025 by Baltic Fire Laboratories. More on the BS 8458 change →

Common reasons a proposal gets sent back

  • Cupboards or pantries with doors larger than 2 m² aren’t covered.
  • Hallways wider than 1 m aren’t covered.
  • The design departs from BS 9991 without a fire engineering report to support it.

We check for these at the design stage, so they don’t hold up your build.

When you’ll need a fire engineer

Recent changes to the regulations have created some grey areas, and Automist isn’t always the whole answer on its own. You’re likely to need a fire engineer if:

  • The room is larger than the system has been tested for. Plumis’s fire testing covers rooms up to 80 m² with ceilings up to 3.5 m.
  • The building is tall. In England, blocks of flats over 11 m normally need sprinklers, and Building Control or the relevant authority will decide whether water mist can be used.
  • The project is in Scotland, where every use of Automist needs a site-specific submission to the local verifier.

A fire engineer can justify a design using performance-based fire engineering (BS 7974). We work with fire engineers who know the system and can bring them in.

What you’ll get from us

  • A system design and layout drawing for your submission.
  • Product and test information for Building Control.
  • A certificate when the system is installed and commissioned.

Watch: Automist being fire-tested to BS EN 14972-17 at Baltic Fire Laboratories (Plumis).

Send us your drawings (a photo of them is fine) and we’ll come back with a design and a full quote, usually before anyone needs to visit site. Send your plans →

Please note: as an authorised installer we design to the brief we’re given, but we can’t decide what fire protection your property needs. That decision, and final sign-off, rests with Building Control or the relevant authority.